MKEG

Addressable Fire Alarm Systems

[1] N3060

– 1 to 12 loops per FACP
– 127 or 255 addresses per loop selectable
– Max. 3,060 addresses per FACP
– 10.4 inch color touch screen
– MAX. 64 nodes per network
– NFPA Class A, B, and X (Style 4, 6, and 7)for SLC
– 4 NACs, 6.0A in total (optionally expandable up to 16A with an additional power supply unit
– 4,000 events history buffer
– 110 to 240V, 50/60Hz for AC universal input
– 12Ah to 65Ah back up battery capacity
– UL listed

[2] N765

– 1 or 3 loops per FACP
– 127 or 255 addresses per loop selectable
– Max. 765 addresses per FACP
– 160 characters LCD (40 letters x 4 lines
– MAX. 64 nodes per network
– NFPA Class A, B, and X (Style 4, 6, and 7) for SLC
– 2 NACs, 5.0A in total
– 4,000 events history buffer
– 100 to 240V, 50/60Hz for AC universal input
– 7Ah to 40Ah back up battery capacity
– UL listed

[1] LCD-type remote annunciator,
FIRU009-R-LCD

– 40 letters x 4 lines LCD
– 11 status LEDs
– Key lock switch to protect system control switch operation
– 6 system control switches
– Built-in buzzer
– 24VDC for rated operating voltage
– UL listed

[2] LED-type remote annunciator,
FIRU009-R-LED

– 16 zones status indicators
– 6 system status LEDs
– Key lock switch to protect system control switch operation
– Built-in buzzer
– 24VDC for rated operating voltage
– UL listed

[3] LED driver module for mimic panel,
PCA-N3060-LDM

– 32 LED driver outputs for zone status indications
– Consecutive or random zone number assignment available
– Audible alarm device (Built-in buzzer)
– Power supply status LED and signal transmission status LED
– 24VDC for rated operating voltage
– UL listed

Analog photoelectric smoke detector, FDKU033-D & FDKU033-D-X

– Very low profile (28.7mm/1.13 inch only in height)
– Wide alarm set-point range 5.1 to 11.0 %/m (1.57 to 3.50 %/foot)
– True analog detector
– UL listed smoke calibration and sensitivity
– IP42
– Simple and accurate address setting without mechanical switches
– LEDs for 360° viewing
– 22.0 to 24.OV for working voltage range of SLC
– UL listed (UL268 7th Edition)

Analog fixed temperature heat detector, FDLU019-D-X

– Very low profile (30.7mm/1.21 inch only in height)
– 57°C to 85°C (135°F to 185°F) heat sensor
– True analog detector
– Ambient temperature listing of 0°C to 66°C (32°F to 150°F)
– Simple and accurate address setting without mechanical switches
– LEDs for 360° viewing
– 22.0 to 24.OV for working voltage range of SLC
– UL listed

Analog rate-of-rise/fixed-temp. combination heat detector, FDHU003-D-X

– Very low profile (30.7mm/1.21 inch only in height)
– 57°C to 79°C (135°F to 174°F) heat sensor
– True analog detector for fixed temperature
– Rate-of-rise feature
– Rate-of-rise operates when the temperature increases 7°C to 8°C (12°F to 15°F) per minute occurs
– Simple and accurate address setting without mechanical switches
– LEDs for 360° viewing
– 22.0 to 24.OV for working voltage range of SLC
– UL listed

Analog photoelectric projected beam smoke detector, FDGJ002-D-X
  • – Wide and high coverage within 100m distance
  • – Sensitivity drift compensation for contamination or a slight shift in the optical system
  • – Light synchronized system to prevent false alarms
  • – Simple optical axis setting
  • – Simple and accurate address setting without mechanical switches
  • – 24VDC for rated operating voltage of SLO
2-terminal base, FZBU013-2Z

– Standard 2-wire detector base
– UL listed (UL268 7th Edition)

4-terminal base, FZBU013-4Z

– Standard 2-wire system with remote indication circuit
– UL listed (UL268 7th Edition)

Isolator base, FZBU005-AIB

– Short circuit isolator integrated in detector base
– Self-restoring
– Optional locking tab to prevent unwanted removal
– 22.0 to 24.OV for working voltage range of SLC
– UL listed (UL268 7th Edition)

Sounder base, FZBU005-ASB

– Integrated sounder in detector base
– Sound output at 75 dB (UL 464 listed)
– Sounder independent of detector
– May be mapped to any device connected to the control panel
– Simple and accurate address setting without mechanical switches
– Optional locking tab to prevent unwanted removal
– 22.0 to 24.OV for working voltage range of SLC
– UL listed (UL268 7ih Edition)

Twin Relay Module, FRRU004-TRM4
  • Dry contact addressable module
  • Two typical form C dry contacts at 24VDC 2A, 125VAC 0.5A
  • One simple LED for status indication
  • 22.0 to 24.0V for working voltage range of SLC
  • Simple and accurate address setting without mechanical switches
  • UL listed
Miniature Contact Module, FRRU004-MCM
  • Input signal addressable module, mini-size
  • NFPA Class B (Style B) for IDC
  • 5.1KQ, 1/2W end-of-line resistor for IDC
  • 22.0 to 24.0V for working voltage range of SLC
  • Simple and accurate address setting without mechanical switches
  • UL listed
Single Contact Module, FRRU004-SCM4
  • Input signal addressable module
  • One simple LED for status indication
  • NFPA Class B (Style B) for IDC
  • 5.1kQ, 1/2W end-of-line resistor for IDC
  • 22.0 to 24.0V for working voltage range of SLC
  • Simple and accurate address setting without mechanical switches
  • UL listed
Dual Contact Module, FRRU004-DCM4
  • Input signal addressable module, two inputs
  • One simple LED for status indication
  • NFPA Class A (Style D) and Class B (Style B) for IDC
  • One address in Class A, two addresses in Class B for IDC
  • 5.1KQ, 1/2W end-of-line resistor for IDC in Class B
  • 22.0 to 24.0V for working voltage range of SLC
  • Simple and accurate address setting without mechanical switches
  • UL listed
Conventional Initiating Zone Module, FRRU004-CIZM4
  • Addressable module for conventional detectors
  • One simple LED for status indication
  • NFPA Class A (Style D) and Class B (Style B) for IDC
  • 15.7 to 22.6V output voltage range of DC
  • 5.1KQ, 1/2W end-of-line resistor for IDC in Class B
  • 22.0 to 24.0V for working voltage range of SLC
  • Simple and accurate address setting without mechanical switches
  • UL listed
Monitored Output Module, FRRU004-MOM4
  • Wet output addressable module
  • One simple LED for status indication
  • NFPA Class B (Style Y) for NAC
  • UL listed with potter/Amesco®, GENTEX®, and Cooper Wheelock® syncro-modules and devices
  • 24VDC, 2A rating for connected device power (releasing device and NAC)
  • 5.1KQ, 1/2W end-of-line resistor value for notification appliance
  • 5.1KQ, 1/2W with diode, end-of-line device for releasing device
  • 22.0 to 24.0V for working voltage range of SLC
  • Simple and accurate address setting without mechanical switches
  • UL listed
Short Circuit Isolator, FQIU004-SCI
  • One simple LED for status indication
  • Self-restoring LED indication
  • 22.0 to 24.0V for working voltage range of SLC
  • UL listed
Analog Input Module, FRRU004-AIM
  • One simple LED for status indication
  • Monitors the analog input of 4 to 20mA
  • 0.5A rating for connected device
  • 22.0 to 24.0V for working voltage range of SLC
  • Simple and accurate address setting without mechanical switches
  • UL listed
Gas Suppression Control Unit, FRRU004-GSCU
  • Field control unit for gas suppression systems
  • Two addresses
  • Programmable NAC, DI (discharge Indicator), abort, and manual release circuits
  • NFPA Class B (Style B) for IDC and Class B (Style Y) for NACs and DI
  • 2 NACs and 1 DI, 3.0A in total
  • 5.1kQ, 1/2W end-of-line resistor for IDC and NACs and DI
  • Equipped with changeover switch (Auto & Manual or Manual only) and countdown timer
  • Status LEDs for power input, changeover switch, abort, manual release, trouble, suppression disabled, pre-discharge, discharge
  • 22.0 to 24.0V for working voltage range of SLC
  • Simple and accurate address setting without mechanical switches
  • UL listed
Wet Output Module 4-Circuit, 1 Address, FRRJ001A-Y-S
  • 1 address with 4 circuits
  • Return signal per circuit for device activation confirmation
  • Circuits applicable to input signals
  • 2A maximum voltage output per circuit
  • Dry typical form A contact for return signal
  • 24.0V for rated operating voltage of SLC
  • Simple and accurate address setting without mechanical switches
  • Slim unit
Wet Output Module 16-Circuit, 4 Address, FRRJ001-Y-4S
  • 4 addresses with 16 circuits
  • Return signal per circuit for device activation confirmation
  • Circuits applicable to input signals
  • 2A maximum voltage output per circuit
  • Dry typical form A contact for return signal
  • 24.0V for rated operating voltage of SLC
  • Simple and accurate address setting without mechanical switches
  • Slim unit
Dry Contact Module 4-Circuit, 1 Address, FRRJ001A-Y-SS
  • 1 address with 4 dry contacts and 4 inputs
  • Return signals or input signals available
  • Dry typical form A contact at 30VDC, 2A railing
  • 24.0V for rated operating voltage of SLC
  • Simple and accurate address setting without mechanical switches
  • Slim unit
Dry Contact Module 8-Circuit, 2 Address, FRRJ001-Y-2SS
  • 2 addresses with 8 dry contacts and 8 inputs
  • Return signals or input signals available
  • Dry typical form A contact at 30VDC, 2A railing
  • 24.0V for rated operating voltage of SLC
  • Simple and accurate address setting without mechanical switches
  • Slim unit
Dry Contact Module 16-Circuit, 4 Address, FRRJ001-Y-4SD
  • 4 addresses with 16 dry contacts
  • Dry typical form A contact at 30VDC, 2A railing
  • 24.0V for rated operating voltage of SLC
  • Simple and accurate address setting without mechanical switches
  • Slim unit
Addressable Module for Initiating Device 4 Address, FRRJ001-Y-4F
  • 4 consecutive addresses per unit
  • NFPA Class B (Style B) for IDC
  • MK-G conventional fire detectors compatible
  • 24.0V for rated operating voltage of SLC
  • Simple and accurate address setting without mechanical switches
  • Slim unit
Addressable Module for Initiating Device 16 Address, FRRJ001-Y-16F
  • 16 consecutive addresses per unit
  • NFPA Class B (Style B) for IDC
  • MK-G conventional fire detectors compatible
  • 24.0V for rated operating voltage of SLC
  • Simple and accurate address setting without mechanical switches
  • Slim unit
System monitoring program, CNI016N

– Max. 195,840 addresses configurable per SMP
– Max. 64 nodes available on network
– Remote monitoring of networked system via VPN
– Max. 1,000,000 symbols available per SMP
– DXF & BMP data applicable to floor plans
– Group functionality same as FACP
– Current event list
– Event log for up to 50,000 events per SMP
– Analog value trend indication
– Sensor monitoring
– 4 system control switches
– Designed for Microsoft Windows 8 and 10

System interface unit, CSC004

– NFPA Styles 4 and 7 wiring applicable
– Max. 64 nodes available on network
– Max. length between two nodes as
600m for copper/metal cable, 2,000m
for 50/125 fiber optic cable, 1,700m for
62.5/125 fiber optic cable, and 5,000m
for 9/125 fiber optic cable
– Status LEDs
– 110V and 240V for AC universal input

FZAW004-P

– Electric address setting compatible with all MK-G addressable devices